
Learn transformer differential protection calculations for a 26 MVA, three-phase 132/12 kV transformer, focusing on data collection, current calculation, and current compensation in the relay.
Learn transformer differential protection calculations for SEL 787: transform ratio, CT matching, vector group D y 11, differential current, impedance, and tap changer effects.
Explain how current and voltage transformers use CT ratios to feed transformer differential protection and delineate the zone of protection from CTs through SF6 bushings to connected cables and switchgear.
Demonstrates how current transformers connect to transformer differential protection, detailing multi-ratio CTs, terminal blocks, test blocks, and star-point wiring to relay Z01, 3, 5.
Learn to compute transformer full-load currents for differential protection, using a 26 MVA rating and 132 kV / 12 kV voltages for HV and LV amperes.
Identify and correct an error in LV full-load current calculations for a transformer, verifying the LV side current as 1250.96 A using the voltage ratio and nameplate data.
Analyze how on-load tap changer variations cause non-fixed voltage ratios and corresponding current changes, and learn to compensate for these errors in transformer differential protection calculations.
Explore differential protection characteristics of a transformer differential relay 87, comparing operating and restraining currents, using slope-based regions and pickup values to stabilize against current transformer saturation and faults.
Explore how transformer percentage impedance limits fault current and determines fault MVA, enabling calculation of short-circuit current on hv and lv sides and its relevance to differential protection.
Learn how to perform tab and per-unit calculations for SEL 787 differential protection, including CT ratios, star and delta connections, vector group matching, phase angle compensation, and tab settings.
Dear All,
Trainer Introduction:
Your trainer brings over 21 years of experience in operation & maintenance, erection, testing, project management, consultancy, supervision, substation automation, SCADA, and commissioning. With a background spanning power plants, high voltage substations, and HVDC installations, he has worked with renowned organizations such as Siemens Saudi Arabia. He has been involved in over 20 high-voltage substation projects across Pakistan and Saudi Arabia.
His expertise encompasses a wide range of areas including protection systems, substation automation systems, design, testing, and commissioning of power generation systems, high voltage switchgear, protection relays, and control schemes. He has a proven track record of leading testing and commissioning teams for implementing electrical infrastructure projects for industrial clients, including steel and petrochemical industries.
Protection Element Setting:
Functional Scope:
The SEL-787 has three differential elements (87R-1, 87R-2, and 87R-3).These elements employ
Operate (IOP) and Restraint (IRT) quantities that therelay calculates from the winding input currents.
Figure shows the relay characteristic. You can set the characteristic as either a single-slope, percentage differential characteristic or as a dual-slope, variable-percentage differential characteristic. Tripping occurs if the Operate quantity is greater than the curve value for the particular restraint quantity.
A minimum pick up level for the Operate quantity must also be satisfied.
The four settings that define the characteristic are:
O87P = minimum IOP level required for operation
SLP1 = initial slope, beginning at the origin and intersecting O87P at
IRT = O87P • 100/SLP1
IRS1 = limit of IRT for SLP1 operation; intersection where SLP2 begins
SLP2 = second slope must be greater than or equal to SLP1
The relay (SEL-787) use the transformer MVA rating as a common reference point, TAP scaling converts all secondary currents entering the relay from the two windings to per unit values, thus changing the ampere values
into dimensionless multiples of TAP. Throughout the text, the term “TAP” refers to the per-unit value common to
both windings. This method ensures that, for full-load through-current conditions, all incoming current multiples of
tap sum to 1.0 and all outgoing current multiples of tap sum to –1.0, with a reference direction into the transformer windings.
In this course, we will perform the setting calculation of 26MVA transformer with following data:
Type of cooling : ONAN / ONAF
Vector Group : Dyn11
Rated Voltage HV V : 132000
Rated Voltage LV V : 12000
Full Load current HV A : 87.48 / 113.72
Full Load current LV A : 1004.12 / 1305.35
Rated Power MVA : 20 / 26
% impedance at normal tap (12 no.) : 15.35% / 19.95 %
Type of tap changer : On load
Voltage at maximum tap V : 151800
Voltage at minimum tap V : 112200
Further we will calculate:
Protection Settings Calculations for Power Transformers
Full load amperes
Short circuit MVA
Short circuit current at HV & LV sides
relationship between short circuit MVA and percentage impedance of transformer
Magnitude and phase angle error and its compensation
CT error and its compensation
Operating and restraining currents
Pickup current calculations
TAPN calculations
Phase angle compensation settings
Slope 1 & 2 calculations
Harmonics blocking calculations.
Best Regards