Main points that covered in the course :
1- We will present some types of level measurement instruments.
There are two main categories:
- Point level instruments, which produce digital signals and are used to detect a specific level (such as full or empty).
- Continuous level instruments, which produce analog signals and measure the level across a range.
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
2- Case study tutorial :
How to measure fluid level of open vessel using ultrasonic level (non contact sensor)
Open vessel : Tank level control system is widely used in automation , common application in industry .
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
3- we have 4 points in open vessel application :
a. Features and conditions of the open vessel – understanding the design and environment of the tank.
b. Mounting the ultrasonic sensor and installation conditions – where and how to properly install the sensor.
c. Entering variables into the transmitter – this step is known as programming or commissioning.
d. how to connect the sensor & the transmitter using terminal blocks and electrical wiring. Proper wiring ensures accurate signal transmission and safe operation.
main points of course :
1. physical quantities: know the physical quantities measured by the sensor.
2.physical theories : understand the different types of sensors, the physical theories behind them, their operating principles, and how they function.
3. Application: Indicates where the instrument should be installed for example at (a pipe , open channel ,lake ,river ,vessel ,tank , etc )
4. Installation : Describes the appropriate installation location for the instrument.
5. Configuration / programming : Edit the device parameters, such as maximum and minimum levels, tank shape, and nominal pipe size, inside diameter, wall thickness .
6. operation.
7. Commissioning: involves installing the system, verifying its operation, performing necessary tests, and delivering the fully functional system to the client.
8. Tenders and bids: include the preparation of technical specifications, identification of product features and requirements, evaluation of different types of equipment, and selection of the most suitable solution."
9. integration with plc
10. Output control
11. Communication
Level sensors divided in to 2 classifications :
1.Point level measurement as level switch , level electrode , float switch :
give digital signal to plc.
Capacitive , optical , float , conductive.
Invasive to a product :they must touch the product.
2. Continuous level measurement as level meter , :
Give certain level measurement such as 5 m , 45 ft , 22 inches.
Non-contact sensor / non-invasive : don’t touch the product.
Continuous level transmitters can be installed for the following applications:
Flumes or weirs.
Ponds/ rivers/lakes.
Open or closed vessel /tank.
Case study :
How to measure fluid level of open vessel using ultrasonic level (non contact sensor)
We show u how to install/mount level sensor in top of the vessel , ultrasonic type .
Uses level switches / level transmitters to detect the water level.
Notice the following features/ conditions of vessel:
you have to know these info about the interested tank
Product type : liquid , paste like, solids
Tank shapes :
Process conditions : specify the product conditions
blocking distance:
mode : level / ullage
filling inlets/holes
overflow holes at high level
Zero point /min : fixed reference point near the bottom of the vessel.
variables of vessel 1:
use meter tape to get these values/ documents such as P&ID diagram for this vessel
product : water
tank shape: flat ceiling
Hight of vessel : 6 m from zero reference point
Diameter /width : 4 m
Installed pipe of a pump: about 1 m from zero reference of vessel, supply pump / draw pump
to install level switches on pipe of pump to avoid dry running of pump & keep liquid level above this point by level transmitter .
No overflow hole
supply inlet pipe: at 3 m from zero reference point
Empty E : 5.4 m from zero reference point
Full F/ span : 5.1 m from zero reference point
the distance from the minimum level to the maximum level
Bd (block distance) : 0.3 m from sensor membrane.
Max level according to process needs : 1.85 m relay activated to start a pump via plc/transmitter itself
Min level according to process needs: 1.14 m relay deactivated to stop pump
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
variables of vessel 2:
Hight of vessel : 6 m from zero reference of vessel,
Diameter /width : 8 m
Supply inlet pipe : at 2 m from zero reference of vessel,
Installed pipe of a pump: about 1.5 m from zero reference of vessel, supply pump / draw pump
to install level switches on pipe of pump to avoid dry running of pump & keep liquid level above this point by level transmitter .
Overflow hole : at 4.5 m
Empty E : 5.4
Full F : 5.1 m
Bd (block distance) : 0.3 m
desired level according to process needs : 4.4 m relay activated to start alarm
desired level according to process needs : 4.3 m relay deactivated to stop alarm/horn
Installation conditions for on vessel for level measurement
Installation conditions for flow measurement.
,,,,,,,,,,,,,,,,,,,,,
1. Mounting FDU 9x sensor on a vessel: go to the attached catalogue of sensor , called (installation)
with link :fdu91.pdf
go to page number 15 .
Ultrasonic level sensor is fixed at top of tank filled with liquid , the reference point for all measurements is the bottom of tank, zero reference point.
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
2. Power supply for ultrasonic sensors/ connecting to transmitter FMU:
go to the attached catalogue of sensor , called (commissioning)
with link : fmu90 comission.pdf
go to page number 24.
We have 2 versions ,so u can power with 220/24 volts
Fuse will be 400/ 2.
1. after mounting / install sensor fdu90 from Endress Hauser, in the last lesson .
2. Connect this sensor cables with transmitter fmu90 , i show you terminal blocks & electrical wiring .
3. Switching on the measuring device.
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
4. Elements of the display and operating module:
i show u the main interface of fmu90 transmitter from Endress + hauser brand,
- Soft key symbols
- Soft shortcut menus at LCD such as (info , menu).
- Keys.
- Light emitting diodes to indicate the relay switching states
- LED to indicate the operational state
- Display symbols
- Parameter value with unit (here: primary value)
note : go to (Commissioning & edit parameters pdf , attached to this lesson) page 44 .
Configuring the measuring device:
- press right hard key to get to : menu soft key
main menu screen appear with these submenus:
- level
- safety settings
- relay/control
- output/calculate
- device properties
- system informat
- display
- sensor management
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
go to level menu , then u see 3 submenus
- basic set up
- extended calibration
- simulation
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
then go to basic set up menu:
Navigation1
Level → Level (LVL) N → Basic setup → LVL N sensor sel.
parameters
input : sensor 1
sensor selection : automatic
detected : fdu 91
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
Navigation2
Level → Level (LVL) N → Basic setup → LVL N app. para.
parameters
• Tank shape
• Medium property
• Process condition
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
Navigation3
Level → Level (LVL) N → Basic setup → LVL N empty cal.
parameters
Parameter "Empty E"
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
Navigation 4
Level → Level (LVL) N → Basic setup → LVL N full cal.
Parameter
• Full F
• Blocking distance
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
Navigation5
Level → Level (LVL) N → Basic setup → LVL N unit
parameter
• Unit level
• Level N
• Sensor
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
note : go to (Commissioning & edit parameters pdf , attached to this lesson) page 50 to 52
Access to the operating menu via the local display:
Elements of the display and operating module:
Configuring the measuring device:
before this step u have to connect fdu90 sensor cables with transmitter.
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
Elements of the display and operating module
i show u the main interface of fmu90 transmitter from Endress + hauser brand:
1Soft key symbols
soft shortcut menus at lcd:info , menu
2 Keys
3 Light emitting diodes to indicate the relay switching states
4 LED to indicate the operational state
5 Display symbol
6 Parameter value with unit (here: primary value)
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
Symbols for operating state
User operating state: soft symbol of wrench
User parameters can be edited. Service parameters cannot be edited.
locked operating state: soft symbol of key
All parameters are locked and cannot be edited.
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
General key combinations:
left & middle hard keys : escape /back
three hard keys in the same time : lock or unlock screen /cant edit parameters
leds on face plate
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
Left button ("Info") : shortcut menu
Provides fast access to the most important parameters:
• Daily counter
• Tag marking
• Envelope curve
• Language
• Device information
• Password/reset
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
• Right key ("Menu"): main menu
Contains all the parameters of the device, subdivided into submenus and parameter sets.
level
safety settings
relay/control
output/calculate
device properties
system informat
display
sensor management
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
how can u navigate through submenus?
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
note : go to Commissioning pdf page 44
Main points that covered in the course :
1- We will present some types of level measurement instruments.
There are two main categories:
- Point level instruments, which produce digital signals and are used to detect a specific level (such as full or empty).
- Continuous level instruments, which produce analog signals and measure the level across a range.
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
2- Case study tutorial :
How to measure fluid level of open vessel using ultrasonic level (non contact sensor)
Open vessel : Tank level control system is widely used in automation , common application in industry .
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
3- we have 4 points in open vessel application :
a. Features and conditions of the open vessel – understanding the design and environment of the tank.
b. Mounting the ultrasonic sensor and installation conditions – where and how to properly install the sensor.
c. Entering variables into the transmitter – this step is known as programming or commissioning.
d. how to connect the sensor & the transmitter using terminal blocks and electrical wiring. Proper wiring ensures accurate signal transmission and safe operation.
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
4- after mounting / install sensor fdu90 from Endress Hauser, in the last lesson .
- Connect this sensor cables with transmitter fmu90 , i show you terminal blocks & electrical wiring .
- Switching on the measuring device.
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
5- Access to the operating menu via the local display:
Elements of the display and operating module:
Configuring the measuring device:
i show u the main interface of fmu90 transmitter from Endress + hauser brand:
1- Soft key symbols
soft shortcut menus at lcd:info , menu
2- Keys
3- Light emitting diodes to indicate the relay switching states
4- LED to indicate the operational state
5- Display symbol
6- Parameter value with unit (here: primary value)
Symbols for operating state
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
6- press right hard key to get to : menu soft key
main menu screen appear with these submenus:
- level
- safety settings
- relay/control
- output/calculate
- device properties
- system informat
- display
- sensor management
go to level menu , then u see 3 submenus
- basic set up
- extended calibration
- simulation
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,